MODEL CUB5 - MINIATURE ELECTRONIC 8-DIGIT DUAL
COUNTER AND RATE INDICATOR
C UR L US LISTED
IND. CONT. EQ.
51EB
LCD, REFLECTIVE OR GREEN/RED LED BACKLIGHTING
0.46" (11.7 mm) HIGH DIGITS
OPTIONAL SETPOINT OUTPUT CARD
OPTIONAL SERIAL COMMUNICATIONS CARD (RS232 or RS485)
OPTIONAL USB PROGRAMMING CARD
OPERATES FROM 9 TO 28 VDC POWER SOURCE
PROGRAMMABLE SCALING FOR COUNT AND RATE
BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL
QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION)
BUILT-IN BATCH COUNTING CAPABILITY
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
NEMA 4X/IP65 SEALED FRONT BEZEL
GENERAL DESCRIPTION
The CUB5 provides the user the ultimate in flexibility, from its complete user
programming to the optional setpoint control and communication capability.
The meter can be programmed as a single or dual counter with rate indication
capability. The display can be toggled either manually or automatically between
the selected displays.
The CUB5 display has 0.46" (11.7 mm) high digits. The LCD is available in
two versions, reflective (CUB5R000) and backlight (CUB5B000). The backlight
version is user selectable for green or red backlighting with variable display
intensity.
The counter is programmable for one of eight different count modes,
including bi-directional and quadrature. When programmed as a dual counter,
each counter has a separate scale factor and decimal points. In the counter/rate
indicator mode, each have their own scaling and decimal point read-outs in
different engineering units. The internal batch counter can be used to count
setpoint output activations.
The meter has two separate inputs which provide different functions
depending on which operating mode is selected. Input A accepts the signal for
the Count and/or Rate displays, while Input B accepts the signal for the Count
display or direction control. In the anti-coincidence mode, both inputs are
monitored simultaneously so that no counts are lost. The resulting display can
be chosen as the sum or difference of the two inputs. The Rate Indicator has
programmable low (minimum) and high (maximum) update times to provide
optimal display response at any input frequency. There is a programmable user
input that can be programmed to perform a variety of functions.
The capability of the CUB5 can be easily expanded with the addition of
option cards. Setpoint capability is field installable with the addition of the
single setpoint relay output card or the dual setpoint solid state output card.
Serial communications capability for RS232 or RS485 is added with a serial
option card.
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5. The
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the
unit and sensors.
COUNTER
The CUB5 receives incoming pulses and multiplies them by the Count Scale
Factor to obtain the desired reading for the count display. Input A accepts the
signal for the count and Input B is used for quadrature, dual counter, anti-
coincidence counting, or up/down control counting.
RATE
The rate indicator utilizes the signal at Input A to calculate the rate value
using a time interval method (1/tau). The unit counts on the negative edge of the
input pulses. After the programmed minimum update time elapses and the next
negative edge occurs, the unit calculates the input rate based on the number of
edges that occurred during the elapsed time. The input rate is then multiplied by
the rate scaling value to calculate the rate display.
At slower rates, averaging can be accomplished by programming the rate
minimum update time for the desired response. Extensive scaling capabilities
allow practically any desired reading at very slow count rates.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to
installationand operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
.13 (3.3)
9876543.2 1.54(39.1)
SEL RST
2.95 (74.9)
.15 (3.8)
1.29 (32.8)
1.71
(43.4)
1
ON ECE
12 3 4
1.30
+.024
-.000
(33
+6
-0
)
2.68
+.025
-.000
(68
+8
-0
)

1 page




CUB5SNK0 pdf
4.3 INPUT WIRING
CAUTION: Power common (PWR COMMON) is NOT isolated from input common (INP COMM). In order to preserve the safety of the meter
application, the power common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth
ground potential. If not, hazardous voltage may be present at the Signal or User Inputs and input common terminals. Appropriate considerations must
then be given to the potential of the input common with respect to earth ground; and the common of the plug-in cards with respect to input common.
Magnetic Pickup
Input A
AC Inputs From Tach Generators, Etc.
Input A
Two Wire Proximity, Current Source
Input A
ON
*
12 34
MAGNETIC PICKUP
PWR COMMON
Current Sinking Output
+9-28 VDC
Input A
ON
**
12 34
Resistor to Limit Current
to 2.5 mA MAX.
AC
PWR COMMON
+9-28 VDC
Current Sourcing Output
Input A
ON
**
12 34
2.2 k Ω
PWR COMMON
Interfacing With TTL
+9-28 VDC
Input A
ON
**
12 34
ON
NPN
O.C.
**
12 34
ON
PNP *
O.C.
12 34
+5 V
COMMON
PWR COMMON
+9-28 VDC
Switch or Isolated Transistor; Current Sink
Input A
PWR COMMON
+9-28 VDC
PWR COMMON
+9-28 VDC
Switch or Isolated Transistor; Current Source Current Sink Output; Quad/Direction
Input A
ON
**
12 34
ON
**
12 34
PWR COMMON
+9-28 VDC
PWR COMMON
Switch position is application dependent.
4.4 SETPOINT (OUTPUT) WIRING
SINGLE SETPOINT RELAY PLUG-IN CARD
COM
N.O.
N.C.
+9-28 VDC
ON
12 34
PWR COMMON
+9-28 VDC
Shaded areas not recommended for counting applications.
ELECTRICAL CONNECTIONS
COM N.O. N.C.
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD
COM
OSNK1
OSNK2
ELECTRICAL CONNECTIONS
OSNK 1(2)
(30 V MAX.)
COM
Note: Output Common is not isolated from DC Power Common. Load must
be wired between OSNK terminal and V+ of the load supply.
4.5 SERIAL COMMUNICATION WIRING
SERIAL COMMUNICATIONS PLUG-IN CARD
4.6 USB PROGRAMMING
USB PROGRAMING PLUG-IN CARD
654321
65 4 3 2 1
RS485
RS232
RJ11 CONNECTOR PIN OUTS
5

5 Page





CUB5SNK0 arduino
6.4 MODULE 4 - Setpoint Output Parameters (4-SEtPt)
4-SEtPt
SEL
SPt SEL
Setpoint
Select
SP2 Only
SP2 Enb
Setpoint 2
Enable
SPn ASN
Setpoint
Assignment
PARAMETER MENU
SPn ACt
Setpoint
Output
Action
SPn tOUt
Setpoint
Output
Time-out
SPn VAL
Setpoint
Value
SPn OUt
Setpoint
Output Logic
SPn LIt
Setpoint
Annunciator
Pro
SP1 Only
SP2 Only
SPn P-UP SPn tYPE SPn StbY SPn AUtO SP1 OFF2 SP2 OFF1 SPn rSt
Backlight
Unit Only
SPn ChC
Setpoint Output
Power-up
State
Setpoint
Boundary
Type
Setpoint
Standby
Operation
Counter
Auto Reset
SP1 Output
Off at SP2
Output
SP2 Output
Off at SP1
Output
Setpoint
Output Reset
with Manual
Reset
Change Display
Color with
Output State
The Setpoint Output Parameters are only active when an optional Setpoint
Output Module is installed in the meter. Some parameters in the menu will not
appear depending on the Setpoint Assignment and Setpoint Output Action. The
Setpoint Parameter Availability chart below illustrates this.
SETPOINT SELECT
SPt SEL
NO NO SP1 SP2
Select the Setpoint Output to be programmed, starting with Setpoint 1. The
"n" in the following parameters reflects the chosen Setpoint number. After
Setpoint 1 is completely programmed, the display returns to SPt SEL. Repeat
steps for Setpoint 2 if both Setpoints are used in the application.
Select NO to exit the Setpoint programming module. The number of Setpoints
available is dependent on the Setpoint option module installed.
SETPOINT 2 ENABLE (SP2 Only)
SP2 Enb
NO YES
NO
SETPOINT OUTPUT ACTION
SPn ACt
LAtCH
LAtCH t-OUt
bOUNd
The parameter selects the action of the Setpoint Output as described in the
chart. Boundary output action is not applicable for Counter B assignment.
SPT ACTION DESCRIPTION
LAtCH Latched Output Mode
t-OUt
bOUNd
Timed Output Mode
Boundary Mode
(High Acting Type)
Boundary Mode
(Low Acting Type)
OUTPUT ACTIVATES
When Count =
Setpoint
When Count =
Setpoint
When Count
Setpoint
When Count
Setpoint
OUTPUT DEACTIVATES
At Manual Reset
(if SPn rSt=YES)
After Setpoint
Output Time-Out
When Count
< Setpoint
When Count
> Setpoint
Select YES to enable Setpoint 2 and access the setup parameters. If NO is
selected, the unit returns to SPt SEL and Setpoint 2 is disabled.
SETPOINT ASSIGNMENT
SPn ASN
Count A Count A Count b
Select the display to which the Setpoint is assigned.
rAtE
SETPOINT PARAMETER AVAILABILITY
PARAMETER
DESCRIPTION
COUNTER ASSIGNMENT (A or B) *
TIMED OUT BOUNDARY LATCH
t-OUt bOUNd LAtCH
SPn tOUt Setpoint Output Time-out Value
Yes No
No
SPn VAL Setpoint Value
Yes Yes Yes
SPn OUt Setpoint Output Logic
Yes Yes Yes
SPn LIt Setpoint Annunciator
Yes Yes Yes
SPn P-UP Setpoint Output Power-up State
No No Yes
SPn tYPE Setpoint Boundary Type
No Yes No
SPn StbY Standby Operation (Low acting only)
No
Yes
No
SPn AUtO Counter Auto Reset
Yes No Yes
SP1 OFF2 SP1 Output Off at SP2 (SP1 only)
Yes No Yes
SP2 OFF1 SP2 Output Off at SP1 (SP2 only)
Yes No Yes
SPn rSt Output Reset with Manual Reset
Yes No Yes
SPn ChC Change Display Color w/ Output State Yes Yes Yes
* BOUNDARY Setpoint Action not applicable for Counter B Assignment
RATE ASSIGNMENT
TIMED OUT BOUNDARY LATCH
t-OUt bOUNd LAtCH
Yes No No
Yes Yes Yes
Yes Yes Yes
Yes Yes Yes
No No Yes
Yes Yes Yes
Yes Yes Yes
No No No
No No No
No No No
Yes No Yes
Yes Yes Yes
11

11 Page







PáginasTotal 16 Páginas
PDF Descargar[ Datasheet CUB5SNK0.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
CUB5SNK0MINIATURE ELECTRONIC 8-DIGIT DUAL COUNTER AND RATE INDICATORred lion
red lion

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar