IR420-D4
TM Installation Bulletin / Reference Guide
This document is intended as a reference guide for installing and using a BENDER IR420-D4 ground
fault detector. This document includes installation, setup, and usage instructions. For complete de-
tails, including installation, setup, settings, and troubleshooting, refer to the IR420-D4 user manual,
document number TBP101012. This document is intended as a supplement and not a replacement to
the complete user manual.
Only qualified maintenance personnel shall operate or service this equipment. These instructions
should not be viewed as sufficient for those who are not otherwise qualified to operate or service this
equipment. This document is intended to provide accurate information only. No responsibility is as-
sumed by BENDER for any consequences arising from use of this document.
Installation
Mounting
IR420-D4 series devices may be DIN rail mounted, or screw mounted using the black clips lo-
cated on the top and bottom of the device. Screw mounting requires an extra black clip (article
number B98060008, sold separately).
Front Panel Display
Wiring - General
The IR420-D4 monitors a single-phase AC ungrounded
system. Refer to Figure 1 for wiring diagram. Use mini-
mum AWG 24, maximum AWG 12 size wire. Refer to
IR420-D4 series user manual for complete technical de-
tails.
! DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
• Disconnect all power before servicing.
• Observe all local, state, and national
codes, standards, and regulations.
4
1 23
1
6
56
7
32
4
1. External supply voltage; 5A fuse
required for internal device pro-
tection (Use two fuses when pow-
ering device with ungrounded
power)
2. Equipment ground connections
3. Connections to monitored system
4. Alarm relay K1: SPDT contact
5. Alarm relay K2: SPDT contact
6. Connection for optional external
test/reset input
Figure 2 - IR420-D4 front display
1. LED “ON” (green): Illuminates when
power is applied to the device. Flashes
when the connection alarm is active.
2. LED “AL1” (yellow): Illuminates when
the prealarm is activated. Flashes when
the connection alarm is active.
3. LED “AL2” (yellow): Illuminates when
the main alarm is activated. Flashes
when CT connection alarm is active.
4. LCD display
5. TEST / UP button: Activates self-test /
scrolls up inside main menu.
6. RESET / DOWN button: Resets device /
scrolls down inside main menu.
7. MENU / ENTER button: Activates main
menu / Confirms (momuntary push) or
goes back a step (held > 1.5 s) inside
main menu.
Dimensions
Dimensions in inches (mm).
5
Figure 1 - IR420-D4 wiring diagram
Wiring - Contacts
Using a normally closed or normally open contact utilizes two factors: wiring out of the proper
terminal, and setting the respective contact to normally energized or deenergized operation.
Refer to the chart below for relay conditions. For changing the energized state of the contact,
refer to “Figure 6 - Contact operation” on the reverse side of this document.
The factory default for relays K1 and K2 is normally deenergized operation.
2.78”
(70.5)
1.87”
(47.5)
1.42” (36)
1.22” (31.1)
Device Relay Conditions
Relay Operation Setting
Device Alarm State
Normally deenergized mode (N/D)
Non-failsafe mode
“N/O”in device settings menu
Energized in the alarm state
Relay will switch when the alarm is
activated.
Power ON, normal state (no alarms)
Power OFF
Power ON, alarm state
Normally energized mode (N/E)
Failsafe mode
“N/C”in device settings menu
Energized in the normal state
Relay will switch when the alarm is
activated, or when supply voltage
to the device is lost.
Power ON, normal state (no alarms)
Power OFF
Power ON, alarm state
K1 STATE
11-12 CLOSED
11-14 OPEN
11-12 CLOSED
11-14 OPEN
11-12 OPEN
11-14 CLOSED
11-12 OPEN
11-14 CLOSED
11-12 CLOSED
11-14 OPEN
11-12 CLOSED
11-14 OPEN
K2 STATE
21-22 CLOSED
21-24 OPEN
21-22 CLOSED
21-24 OPEN
21-22 OPEN
21-24 CLOSED
21-22 OPEN
21-24 CLOSED
21-22 CLOSED
21-24 OPEN
21-22 CLOSED
21-24 OPEN
Menu Flow Chart for Common Settings
Figure 4 through figure on the reverse side of this document contain flow charts for modifying
commonly used features and settings in the IR420-D4’s main menu. Not all available features
are listed in this document. For more information, consult the IR420-D4 user manual.
Menu Legend
DOWN ARROW button
R
UP ARROW button
T
MENU / ENTER button
< 1.5 s Momuntary button push
> 1.5 s Hold button for at least 1.5 s,
then release
Bender Inc. 800.356.4266 / 610.383.9200 [email protected] www.bender.org
Document NAE1018090 05.2012 © Bender Inc. Page 1/1 Side 1/2

1 page





PáginasTotal 2 Páginas
PDF Descargar[ Datasheet IR420-D4.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
IR420-D4Digital Ground Fault Monitor / Ground Detector Ungrounded (Floating) AC SystemsBENDER
BENDER
IR420-D4Installation Bulletin / Reference GuideBENDER
BENDER
IR420-D4-1Digital Ground Fault Monitor / Ground Detector Ungrounded (Floating) AC SystemsBENDER
BENDER
IR420-D4-2Digital Ground Fault Monitor / Ground Detector Ungrounded (Floating) AC SystemsBENDER
BENDER

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar