VME420
Multi-functional monitoring relays for overvoltage,
undervoltage and frequency monitoring
in AC/DC systems with external supply voltage
Product description
The voltage relays of the VME420 series are designed to monitor the frequency, under-
voltage, overvoltage and the voltage between two threshold values (window discriminator
function) in AC and DC systems. The voltages are measured as r.m.s. values. The currently
measured value is continuously shown on the LC display. The measured value leading to the
activation of the alarm relays will be stored. Due to adjustable response times, installation-
specific characteristics, such as device-specific start-up procedures, short-time voltage
fluctuations, etc. can be considered . Device version VME420 requires an external supply
voltage.
VME420
Device features
• Monitoring AC/DC systems for under-
voltage, overvoltage and frequency in
the voltage range of 0…300 V
• Different monitoring functions selectable
< U, > U or < U/> U, < f, > f or < f / > f
• Start-up delay, response delay, delay
on release
• Adjustable switching hysteresis
• r.m.s. value measurement (AC + DC)
• Digital measured value display via
multi-functional LC display
• Preset function (automatic assignment
of basic parameters)
• LEDs: Power On, Alarm 1, Alarm 2
• Measured value memory for operating
value
• Continuous self monitoring
• I nternal test/reset button
• Two separate alarm relays
(gold-plated relay contacts),
one changeover contact each
• N/C or N/O operation and fault
memory behaviour selectable
• Password protection for device setting
• Sealable transparent cover
• Two-module enclosure (36 mm)
• Indication of the system frequency
• RoHS- compliant
Typical applications
• Single -phase voltage and frequency monitoring of machines and electrical installations
• Earth fault monitoring in medium-voltage systems via voltage transformers
• Monitoring of battery systems
• Switching on and switching off at a certain voltage level
Function
Once the supply voltage is applied, the start-up delay “t” is activated. Measured voltage
and frequency values changing during this time do not influenc e the switching state of
the alarm relays.
The devices provide two separately adjustable measuring channels (overvoltage/under-
voltage). When the measuring quantity exceeds the response value (Alarm 1) or falls
below the response value (Alarm 2), the time of the r esponse delays “ton 1/2” begins.
Once the response delay has elapsed, the alarm relays switch and the alarm LEDs light.
When the measuring value exceeds or falls below the release value (response value plus
hysteresis) after the alarm relays have switched, the selected release delay “toff” begins.
When “toff” has elapsed, the alarm relays switch back to their initial position.
When the fault memory is activated, the alarm relays remain in the alarm state until the
reset button R is pressed. When the fault memory is set to continuous mode, the alarm
parameters remain stored, even on failure of the supply voltage.
Preset function
After connecting the device for the first time, the nominal system voltage will be determined
(PrE run), and the response values for overvoltage and undervoltage as well as for under-
frequency and overfrequency will automatically be set. When no voltage is determined
within a nominal system voltage range (PrE run), the response values will be set to the
minimum or maximum voltage. In this case, the message “AL not SET” appears on the
display. As long as no key is pressed, a nominal system voltage is being searched cyclically
(PrE run). If a key is pressed, the search will be interrupted and the message “AL not SET”
disappears. In this case, the appropriate response values have to be set in the menu.
When activating the frequency monitoring function, the preset frequency will automatically
be applied.
Approvals
24 Main catalogue part 3 – 06.2007 / Electronic measuring and monitoring relays
Right to modifications reserved ! – © Dipl.-Ing. W. Bender GmbH & Co. KG, Germany
http://www.Datasheet4U.com

1 page





PáginasTotal 4 Páginas
PDF Descargar[ Datasheet VME420.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
VME420Multi-functional monitoring relaysBender
Bender

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar