240W Single Output Industrial DIN RAIL with PFC Function
SDR-240 series
Features :
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
SPECIFICATION
SEM PQ
I F47
GL
Marine
MODEL
SDR-240-24
SDR-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
PEAK CURRENT
15A
7.5A
PEAK POWER Note.6
360W (3sec.)
OUTPUT RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V
48 ~ 55V
VOLTAGE TOLERANCE Note.3 1.0%
1.0%
LINE REGULATION
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
20ms/230VAC 20ms/115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC 124 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.93/230VAC
0.99/115VAC at full load http://www.DataSheet4U.com/
INPUT
EFFICIENCY (Typ.) Note.8 94%
AC CURRENT (Typ.)
2.6A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.) 33A/115VAC 65A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
Normally works within 110 ~ 150% rated output power for more than 3 sec and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
PROTECTION OVER VOLTAGE
29 ~ 33V
Protection type : Shut down o/p voltage with auto-recovery
56 ~ 65V
OVER TEMPERATURE
95 5 (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
WORKING TEMP.
Note.5 -25 ~ +70 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
VIBRATION
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508, TUV EN60950-1 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
EMC EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
(Note 4) HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A, SEMI F47, GL approved
MTBF
169.3Khrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
63*125.2*113.5mm (W*H*D)
NOTE
PACKING
1.03Kg; 12pcs/13.4Kg/1.06CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. After 30 min. of burn-in.
File Name:SDR-240-SPEC 2008-12-17

1 page





PáginasTotal 3 Páginas
PDF Descargar[ Datasheet SDR-240.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
SDR-240240W Single Output Industrial DIN RAILMean Well
Mean Well

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar