Advanced Digital Temperature Controller
E5AN-H/E5EN-H
(96 x 96 mm and 48 x 96 mm)
www.DataSheet4U.com
CSM_E5AN-H_E5EN-H_DS_E_3_2
A New High-performance Controller: High Resolution, High Speed, and
High Input Accuracy.
Logic Operations and Preventive Maintenance Function. Plus Infrared
Port on Front Panel.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input)
to handle various sensors with one Controller. Models also
available with Remote SP.
• A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the PV or
SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller
using a Control Output ON/OFF Counter.
• Model available with position-proportional control
96 × 96 mm
E5AN-H
48 × 96 mm
E5EN-H
Refer to Safety Precautions for E5@N/E5@N-H.
Refer to Operation for E5@N/E5@N-H for operating
procedures.
Main I/O Functions
Remote SP Input
One
Event Inputs
None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
Thermocouple/Pt input:
±0.1% of PV
Analog input:
±0.1% FS
Sampling Period
60 ms
PF Key
(Programmable
key function)
E5AN-H
E5EN-H
3-level Display
Simultaneously displays set items, such as the
PV, SV, and MV.
5-digit Display with high resolution of 0.01°C
Infrared port
USB
Auxiliary Outputs
• Two
• Three
Computer Support Software
CX-Thermo
Control Output 2
(built-in)
Output Unit
• SSR outputs • Relay output
Voltage output (for driving SSR)
• Current output
• Linear voltage output
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
Models available with
RS-485, RS-422, or
RS-232C
communications
Control Output 1
(built-in)
Output Unit
• SSR outputs • Relay output
Voltage output (for driving SSR)
• Current output
• Linear voltage output
1

1 page




E5AN-H pdf
Specifications
E5AN-H/E5EN-H
www.DataSheet4U.com
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Voltage output
(for driving SSR)
Control
output
Current output
Linear voltage output
Built-in SSR output
Relay output for
position-proportional
control
Auxiliary
output
Number of outputs
Output specifications
Event
input
Number of outputs
External contact input
specifications
Number of operations
Logic
Operations
operations
Output
Work bit
assignment
Transfer
outputs
Number of outputs
Output specifications
Number of inputs
Signal type
RSP
input
Analog input scaling
Accuracy
Input sampling period
Setting method
Indication method
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 Mmin. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
Output Unit (Install the Output Unit (sold separately).)
75 to 250 VAC, 1 A (resistive load)
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min.
Potentiometer input: Must be between 100 and 2.5 kfor maximum open position.
2 or 3 max.
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
2 or 4 (with an E53-AKB)
Contact input: ON: 1 kmax., OFF: 100 kmin.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
8 max.
Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D
(A, B, C, and D are four inputs.)
Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
Output inversion: Possible
One work bit per operation
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary
outputs, or control outputs.
1 max. (Depends on model. Models with transfer output (F in model number)
Current output: 4 to 20 mA DC, Load: 600 max., Resolution at 4 to 20 mA: Approx. 10,000
1
Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Scaling of signal to engineering units (EU)
19,999 to 30,000 (display: 30,000 max.)
(±0.2% of FS) ±1 digit max.
60 ms
Set digitally using keys on the front panel or by using the RSP input.
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40%
AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output
ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling
coefficient adjustment
10 to 55°C (with no condensation or icing), for 3-year warranty: 10 to 50°C
25% to 85%
25 to 65°C (with no condensation or icing)
5

5 Page





E5AN-H arduino
External Connections
Control output 1 and control output 2 are functionally isolated from the internal circuits.
Controllers
Option Units
E5AN-H/E5EN-H
www.DataSheet4U.com
The Temperature Controller is set
for a K-type thermocouple (input
type = 5) by default. An input error
(s.err) will occur if the input type
setting does not agree with the
temperature sensor. Check the
input type.
100 to 240 VAC
24 VAC/VDC (no polarity)
Input power
supply
1
2
21 11
22 12
Control output 1
3
4
23 13
24 14
Control output 2
5
6
25 15
26 16
Auxiliary output 2
7
8
27 17
28 18
9 29 19
Auxiliary output 1
10 30 20
Communications
E53-EN01
RS-232C
11 SD
E53-EN02
RS-422
11 RDB
12 RD
12 RDA
13 SG
13 SG
21 DO NOT USE 21 SDB
22 DO NOT USE 22 SDA
E53-EN03
RS-485
11 B (+)
12 A ()
13 DO NOT USE
E53-AKB
Event Inputs
11
12
EV2
EV1
13
21 B (+)
21
22 A ()
22
Event Inputs
EV2
EV1
CT2
CT1
Potentiometer
O
14
W 15
Auxiliary output 3
CT2
C
16
DO NOT DO NOT
USE
USE
DO NOT
USE
A
B
DO NOT V
USE
DO NOT
USE
mA
B DO NOT DO NOT
USE
USE
Auxiliary output 3
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, input alarm, or Remote
SP Input Error is sent to the
output to which the alarm 1
function is assigned.
Control outputs 1, 2
Control Output Unit
Control outputs 1, 2
Refer to page 4
SSR Outputs
75 to 250 VAC, 1 A
(resistive load)
Models with Position-
proportional Control
Relay output
250 VAC, 1 A
(including inrush
current)
Auxiliary outputs 1, 2, 3
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
Control Output Unit
1
Input power
supply
2
+
3
Output unit
4
+
5
Output unit
6
7
Auxiliary output 2
8
9
Auxiliary output 1
10
SSR Outputs
Models with Position-
proportional Control
Event input/
Transfer output/
Remote SP
1
Input power
supply
2
3
SSR
4
5
SSR
6
7
Auxiliary output 2
8
9
Auxiliary output 1
10
1
Input power
supply
2
Open
3
4
5
Closed
6
7
Auxiliary output 2
8
9
Auxiliary output 1
10
21
22
23
EV3
24
EV4
25
DO NOT USE 26
+
27 4 to 20 mA DC
Transfer output (Load: 600 Ω max.)
28
+
29
Remote SP input 4 to 20 mA DC
30
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
11

11 Page







PáginasTotal 16 Páginas
PDF Descargar[ Datasheet E5AN-H.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
E5AN-HAdvanced Digital Temperature ControllerOmron
Omron

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar