Número de pieza | TH102 | |
Descripción | temperature transmitter | |
Fabricantes | ABB | |
Logotipo | ||
Hay una vista previa y un enlace de descarga de TH102 (archivo pdf) en la parte inferior de esta página. Total 6 Páginas | ||
No Preview Available ! TH 102 / TH 102-Ex
Rail mounted
temperature transmitter,
HART programmable,
Pt 100 (RTD), thermocouples,
electrical isolation
10/11-8.54 EN
I Input
– Resistance thermometer (2, 3, 4-wire circuit)
www.Da–taTShheeremt4oUc.ocuopmles
– Resistance remote signalling unit (0...5000 Ω)
– Voltages, mV (–125...1200 mV)
I Output
– 2-wire technique
– 4...20 mA, HART signal
I 1 or 2 independent channals
I Electrcal isolation (I/O))
I Digital low-drift processing of measurement values
I Customer-specific linearization
I Continuous sensor and self-monitoring
– Parameter saved permanently in EEPROM
– Monitoring of data integrety every 10 s
I Substitution strategy in case of error (NE43)
I Approvals for explosion protection
– intrinsically safe II 2 G EEx [ia] ib IIC T6, mount in zone 1
– II 3 G EEx n A II T6, mount in zone 2
I Input functionality (absolute, differential, average value)
I EMC acc. to EN 50082-2 and NE 21
I Parameterizationg
– PC software application SMART VISION
– Hand held terminals STT 04, HC 275
I 5 years warranty
ABB Instrumentation
1 page TH 102 / TH 102-Ex
Rail mounted temperature transmitter, HART programmable
10/11-8.54 EN
Ordering information
TH 102 / TH 102-Ex
Without Explosion protection:
TH 102
1-channel
TH 102
2-channel
Catalog No
V11517-
1
3
DM
478,00 *
898,00 *
With Explosion protection
TH 102-Ex
1-channel
TH 102-Ex
2-channel
Zone 1
ATEX: II 2 G EEx [ia]ib IIC T6
ATEX: II 2 G EEx [ia]ib IIC T6
5 528,00 *
2 998,00 *
Zone 2 / type N
TH 102-Ex N
1-channel
ATEX: II 3 G EEx n A II T6
TH 102-Ex N
2-channel
ATEX: II 3 G EEx n A II T6
Programming
1-channel
Factory standard parameter
Pt 100, 0...100 °C, 4-wire circut, damping off, direct action characteristic
overranging at sensor or device error (≤ 23,5 mA)
Customer-specific parameter definition, two-channel version
2-channel
Factory standard parameter
Pt 100, 0...100 °C, 4-wire circuit, damping off, direct action characteristic
overranging at sensor or device error (≤ 23,5 mA)
Customer-specific parameter definition, two-channel version
Calibration certificates
without
1-channel 2-point
1-channel 9-point
2-channel 2-point
2-channel 9-point
N 528,00 *
M 998,00 *
0
1 40,00 *
2
3 60,00 *
0
1 140,00
2 200,00
A 200,00
B 300,00
Accessories
Catalog No
DM
H&B FSK modem [EEx ib] IIC (parameter setting in the installation)
Smart Vision5 Software
on CD-ROM
0343705
7957777
618,00 *
480,00 *
Smart Vision5 manual
31/2" Diskettes
German
7957778
7957779
530,00 *
50,00 *
English
7957780
50,00 *
TH 02 / -102 / -202 driver for AMS software 1.3.1 (Rosemount)
www5.DseaetaDSahtaeeSth4eUet.c6o3m-1.20
7957771
200,00 *
Minimum hardware reuqirements: Intel 80486; 66 MHz, 8MB RAM; free hard-disk capacity; Windows 3.x (95, 98, NT)
Notice:
For a lokal programming on the desk can used as Hardware the universal TS02-Programming-Set (without Parasoft).
(see Data Sheet 11-8.17 ordering information accessoriers )
ex stock
Lager
03.2000
Page 5 of 6
5 Page |
Páginas | Total 6 Páginas | |
PDF Descargar | [ Datasheet TH102.PDF ] |
Número de pieza | Descripción | Fabricantes |
TH102 | temperature transmitter | ABB |
Número de pieza | Descripción | Fabricantes |
SLA6805M | High Voltage 3 phase Motor Driver IC. |
Sanken |
SDC1742 | 12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters. |
Analog Devices |
DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares, |
DataSheet.es | 2020 | Privacy Policy | Contacto | Buscar |