DataSheet.es    


PDF DHR-C10 Data sheet ( Hoja de datos )

Número de pieza DHR-C10
Descripción AC/DC Current transducer
Fabricantes LEM 
Logotipo LEM Logotipo



Hay una vista previa y un enlace de descarga de DHR-C10 (archivo pdf) en la parte inferior de esta página.


Total 3 Páginas

No Preview Available ! DHR-C10 Hoja de datos, Descripción, Manual

AC/DC Current transducer DHR-C10
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 0-10V
voltage output.
IPN = 100..1000 A
Electrical data
Primary Nominal
DC & AC Current
IPN (A.t.RMS)
100
200
300
400
500
600
1000
Primary AC Current
Max. Peak Value
IP (A) (*)
600
600
1000
1000
1800
1800
1800
Output voltage
(Analog)
VOUT (VDC)
0-10
0-10
0-10
0-10
0-10
0-10
0-10
R L Load resistance
VC Supply voltage
IC Current Consumption
VSL Output voltage limitation (0-10V)
ÎP Overload capability (Ampere Turns)
Performance data
X
εL
VOE
TCVOE
TCVOUT
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Electrical offset voltage, TA = 25°C
Temperature coefficient of VOE ( 0..+60 °C)
(-40..+70 °C)
Temperature coefficient of VOUT (% of reading)
Response time tp 90% of IPN step
Frequency bandwidth (±1dB)
General data
TA
TS
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
Type
DHR 100 C10
DHR 200 C10
DHR 300 C10
DHR 400 C10
DHR 500 C10
DHR 600 C10
DHR 1000 C10
10
k
+ 20 .. 50 V DC
30 mA
< 14
V
30000
A.t
< ± 1 % of IPN
< ± 1.0 % of IPN
< ± 1.0 % of IPN
± 2.0 mV/K
± 4.0 mV/K
± 0.1
%/K
< 150
ms
DC 20..6000Hz
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
Note :
(*) The Max. Peak AC Current is the highest peak level of the primary signal that is
taken into account for accurate True RMS calculation. Yet the device is designed for
maximum continuous True RMS value equal to IPN, whereas the output is limited by
the above specified output limitation.
Features
VFD and SCR waveforms current
measurement
True RMS output
Panel mounting
Eliminates insertion loss
Insulated plastic case recognized
according to UL94-V0
Advantages
Large aperture for cable up to
Ø32mm
High isolation between primary and
secondary circuits
Easy installation
Applications
VFD Controlled Loads
VFD output indicates how the motor
and attached load are operating.
SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Application domain
Energy and Automation
061128/14
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com

1 page





PáginasTotal 3 Páginas
PDF Descargar[ Datasheet DHR-C10.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
DHR-C10AC/DC Current transducerLEM
LEM

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar