Current Transducer CT 100-S
For very accurate measurements of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Provisional
IPN = 100 A
Electrical data
IP N
I
P
VO U T
K
N
RL
C
L
tC
V
C
IC
V
d
Primary nominal r.m.s. current
Primary current, measuring range
Analog output voltage
Conversion ratio
Load resistance
Capacitance loading
Output short-circuit duration 1)
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
100
0 .. ± 150
5
100 A / 5 V
> 500
5
± 15
90 + VOUT / R L
6
A
A
V
nF
s
V
mA
kV
Accuracy - Dynamic performance data
X Overall accuracy @ I
G PN
- 25°C .. + 70°C
VO
t
r
di/dt
f
Offset voltage @ IP = 0
TA = 25°C
- 25°C .. + 70°C
Response time 2) @ 90 % de I
PN
di/dt accurately followed
Frequency bandwidth (- 3 dB) @ 10 % of IPN
± 0.15
%
Typ Max
± 0.4 mV
± 0.6 mV
400
60
DC .. 250
ns
A/µs
kHz
General data
T Ambient operating temperature
A
TS Ambient storage temperature
m Mass
Standards
- 25 .. + 70
°C
- 40 .. + 85
°C
670 g
EN 50178 : 1997
Notes : 1) If the short-circuit has a duration more than 1 s, the primary current of
the supply voltage must be interrupted for a short time to restore the
transducer to proper working order. The internal protection is done by
PTC resistors
2) With a di/dt of 60 A/µs.
Features
Closed loop (compensated) current
transducer
Insulated plastic case recognized
according to UL 94-V0
Patent pending.
Advanced features
f = 250 kHz
X
G
=
± 0.15 % (- 25°C .. + 70°C).
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
060808/5
LEM
www.lem.com

1 page





PáginasTotal 2 Páginas
PDF Descargar[ Datasheet CT100-S.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
CT100-SCurrent Transducers CT 100-SLEM
LEM

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar