DataSheet.es    


PDF A5350 Data sheet ( Hoja de datos )

Número de pieza A5350
Descripción Ionization Smoke Detector
Fabricantes Allegro 
Logotipo Allegro Logotipo



Hay una vista previa y un enlace de descarga de A5350 (archivo pdf) en la parte inferior de esta página.


Total 9 Páginas

No Preview Available ! A5350 Hoja de datos, Descripción, Manual

A5350
Ionization Smoke Detector with Interconnect
Features and Benefits
Low average standby current for long battery life
Interconnect up to 125 detectors
Piezoelectric horn driver
Guard outputs for detector input
Pulse testing for low battery
Power-on reset (POR)
Internal reverse battery protection
Inverted alarm polarity on DETECT IN
Package: 16-pin DIP (suffix A):
Not to scale
Description
The A5350 is a low-current, BiCMOS circuit providing
all of the required features for an ionization-type smoke
detector. A networking capability allows as many as 125
units to be interconnected so that if any unit senses smoke all
units will sound their alarm. In addition, special features are
incorporated to facilitate alignment and test of the finished
smoke detector.
The internal oscillator and timing circuitry keep standby power
to a minimum by powering down the device for 1.66 seconds
and sensing for smoke for only 10 ms. Every 24 on-off cycles,
a check is made for a low battery condition. By substituting
other types of sensors or a switch for the ionization detector,
this very-low–power device can be used in numerous other
battery-operated safety/security applications.
The A5350 is supplied in a low-cost 16-pin dual in-line plastic
package (DIP). It is rated for continuous operation over the
temperature range of –10°C to 60°C. The Pb (lead) free version
(suffix –T) has 100% matte tin leadframe plating.
Typical Application
To / from
other units
200 Ω
B
1 NC
16
GUARD2
2
I/O
15
DETECT IN
3 A5350
LOW-V SET
14
GUARD1
4 NC
330 Ω 5 LED
SENSITIVITY SET 13
12
OSC CAP
9V
6 VDD
11
HORN2
8.2 MΩ 7 TIMING RES
HORN1 10
1 μF 8 FEEDBACK
9
VSS
200 k Ω
Push
to Test
200 k Ω
4.7 MΩ
A
0.1 μF
4.7 MΩ
A Use an external resistor divider to set
sensitivity for a particular smoke chamber.
B A resistor to VSS or VDD may
be added to this pin to modify
low battery voltage threshold.
C Value of component will vary, based on
the piezoelectric horn used.
1.5 MΩ
C
220 kΩ
C
0.001 μF
C
26110.5 Rev. 5

1 page




A5350 pdf
A5350
Ionization Smoke Detector with Interconnect
ELECTRICAL CHARACTERISTICS1,2 (continued) at TA = 25°C, VDD = 9.0 V, VSS = 0 V, COSCCAP = 0.1 μF,
RTIMINGRES = 8.2 MΩ (unless otherwise noted)
Characteristic
Symbol
Test Conditions
Test Pin
Min.
Typ.
Max.
Units
I/O Current
IIOL No alarm, VI/O = VDD – 2.0 V
IIOH Local alarm, VI/O = VDD – 2.0 V
2
2
25 —
–7.5 —
60
I/O Alarm Voltage
VIH(IO) External “alarm” in
2 3.0 — —
I/O Delay
tr(io) Local or test alarm to I/O active
2
— 3.0 —
1Negative current is dened as coming out of the specied device pin (sourcing).
2Alarm (smoke) condition is dened as VDETECTIN > VSENSITIVITYSET; no alarm (no smoke) condition is dened as VDETECTIN < VSENSITIVITYSET.
μA
mA
V
s
Circuit Description
The A5350 is a low-current, BiCMOS circuit providing all of
the required features for an ionization-type smoke detector. The
alarm polarity on DETECT IN is inverted as compared with typi-
cal ion-type devices. The DETECT IN voltage must rise above
the SENSITIVITY SET voltage in order to cause an alarm.
Oscillator
An internal oscillator operates with a period of 1.67 seconds
during no-smoke conditions. Every 1.67 seconds, internal power
is applied to the entire circuit for 10 ms and a check is made for
smoke. Every 24 clock cycles (approximately 40 seconds), the
LED pin is pulsed and a check is made for low battery by com-
paring VDD to an internal reference. Because very-low currents
are used in the device, the oscillator capacitor at the OSC CAP
pin should be a low-leakage type (PTFE, polystyrene, or polypro-
pylene).
Detector Circuitry
When the voltage on the DETECT IN pin is greater than the volt-
age on the SENSITIVITY SET pin, the A5350 evaluates this as a
smoke condition.
An active guard is provided on GUARD1 and GUARD2, the two
pins adjacent to the detector input, the DETECT IN pin. VGUARD1
and VGUARD2 will be within 100 mV of VDETECTIN. This will
keep surface leakage currents to a minimum and provide a
method of measuring the input voltage without loading the ion-
ization chamber. The active guard amplifier is not power strobed
and thus provides constant protection from surface leakage
currents. The detector input has internal diode protection against
electrostatic damage.
Alarm Circuitry
If smoke is detected, the oscillator period changes to 40 ms and
the horn is enabled. The horn output is typically 160 ms on,
80 ms off. During the off-time, smoke is checked and further
alarm output will be inhibited if smoke is not sensed. During a
smoke condition, the low-battery alarm is inhibited and the LED
is pulsed approximately once every second.
Sensitivity Adjust
The detector sensitivity must be externally set to the individual
characteristics of the ionization chamber by connecting the
Allegro MicroSystems, Inc.
115 Northeast Cutoff
Worcester, Massachusetts 01615-0036 U.S.A.
1.508.853.5000; www.allegromicro.com
5

5 Page










PáginasTotal 9 Páginas
PDF Descargar[ Datasheet A5350.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
A5350Ionization Smoke DetectorAllegro
Allegro
A5350CAIonization Smoke DetectorAllegro MicroSystems
Allegro MicroSystems
A5354CASMOKE DETECTORAllegro MicroSystems
Allegro MicroSystems
A5355CASMOKE DETECTORAllegro MicroSystems
Allegro MicroSystems

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar