DataSheet.es    


PDF IMD550 Data sheet ( Hoja de datos )

Número de pieza IMD550
Descripción Cooling Capacity
Fabricantes temperzone 
Logotipo temperzone Logotipo



Hay una vista previa y un enlace de descarga de IMD550 (archivo pdf) en la parte inferior de esta página.


Total 1 Páginas

No Preview Available ! IMD550 Hoja de datos, Descripción, Manual

IMD 550
Nominal Airflow: 2350 l/s
Cooling Capacity (kW)
Entering Air Temperature 23°C D.B., 17°C W.B.
COIL
1 ROW
4 ROWS
WATER
FLOW
(l/s)
0.40
0.70
1.00
2.00
3.00
4.00
PRESSURE
DROP
(kPa)
6.6
17.6
32.8
9.5
20.6
33.4
5
Total
Sens.
12.5 10.9
16.3 12.3
19.0 13.4
43.9 31.9
49.9 34.5
53.2 36.0
Total = Total Capacity (kW); Sens. = Sensible Capacity (kW)
Note: Cooling capacities are based on the nominal airflow.
ENTERING WATER TEMPERATURE °C
678
Total
Sens.
Total
Sens.
Total Sens.
9
Total
Sens.
11.6 10.6 10.7 10.3 9.9 9.9 9.2 9.2
15.1 11.9 14.0 11.5 12.8 11.0 11.6 10.6
17.8 12.9 16.2 12.3 14.9 11.8 13.4 11.3
40.5 30.5 37.2 29.1 33.8 27.7 30.5 26.4
46.1 32.9 42.3 31.2 38.5 29.6 34.6 28.0
49.5 34.3 45.2 32.5 41.4 30.8 37.0 29.0
Heating Capacity (kW)
Entering Air Temperature 21°C
Note: Heating capacities are total - based on the nominal airflow. Electric Heating option: 18 kW
COIL
WATER
FLOW
(l/s)
PRESSURE
DROP
(kPa)
40
45
ENTERING WATER TEMPERATURE °C
50 55 60 65 70
75
80
1 ROW
0.40
0.80
1.20
4.5
15.4
31.5
14.7 18.6
17.9 22.5
19.6 24.8
22.5 26.3 30.1 34.0
27.2 31.9 36.6 41.3
30.0 35.2 40.2 45.4
37.9 41.7 45.6
46.0 50.7 55.4
50.6 55.8 60.9
Air Handling
l/s - Pa
LOW
600
MED
- - - - l/s - W
3.0
2.5
HIGH
2.0
1.5
1.0
0.5
Sound Levels
Test Conditions: JIS 8616. 1 m ducting with 25 mm insulation.
Sound Pressure Levels are at 1 m from source.
OCTAVE BAND FREQ. Hz
FAN
SPL SWL 125 250 500 1 k 2 k 4 k
SPEED dB(A) dB(A)
SOUND POWER LEVELS dB
LOW 50 60 61 62 60 54 47 45
MED 55 65 65 66 64 58 52 50
HIGH 59 69 69 71 69 63 57 55
7.2A
400 5.6A
4.6A
200
LOW
MED
0
1300
6A
1500 1700 1900
AIR FLOW (l/s)
HIGH
8A
2100
2.5 m/s
11 A
2300
Face Velocity
Note:
1. Air flows given are for a unit with no filter installed.
2. In a free blow application, beware of exceeding
indoor fan motor's full load amp limit.
Dimensions (mm)
Not to Scale
125
1573
MOUNTING CENTRES
1430
OPTIONAL
FILTER BOX WITH
FILTER ACCESS
EACH SIDE
WATER CONNECTIONS:
32 BSP MALE
(HEATING 32 BSP MALE)
Note: Allow 500 mm
minimum clearance
to each access panel
688
OPTIONAL
SPRING MTG
CENTRES
325
ACCESS
PANEL
700
OVERALL
© temperzone limited 2002
1030
1680
OVERALL
600
MOUNTING
STRAP
CENTRES
FAN ACCESS VIA
REMOVEABLE BASE
& DRAIN TRAY,
OR VIA TOP PANEL
ELECTRICAL
CONDUIT HOLES
ELECTRICAL
ACCESS PANEL
65 65
35
150
310
355
DRAIN 28 OD
735 OA
65
555
80
31

1 page





PáginasTotal 1 Páginas
PDF Descargar[ Datasheet IMD550.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
IMD550Cooling Capacitytemperzone
temperzone

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar